Power System Overview
Cabinets
are classified into AC cabinets and DC cabinets according to the types of input
power for cabinets.
The
input power for AC cabinets is AC power. It may be single-phase 220V current or
three-phase 380V AC, but not all input power for devices/modules inside
cabinets is AC. If a cabinet is equipped with AC/DC power components, DC equipment
can be installed into AC cabinets. The input power for DC cabinets is DC power.
It is generally -48V and the input power for devices/modules inside the cabinet
is DC. However, in some cases, if a cabinet is equipped with an inverter (DC/AC
power components), AC devices/modules can also be installed into DC cabinets.
However,
the Power Distribution Specifications for Service and Software Products
DKBA1315-2004.11 determines that only AC devices/modules can be installed
into AC cabinets and only DC ones can be installed into DC cabinets. That is,
AC devices/modules and DC ones cannot be mixed into one cabinet.
The
power supply system for AC and DC cabinets is divided into AC cabinet power
supply system and DC cabinet power supply system. AC cabinet power supply
system is used to supply cabinets with AC power and DC system is to supply
cabinets with DC power.
Inverter and Power Cable
In
the following situations, use inverters:
Customers
cannot provide AC power and they can only provide -48V DC power or the AC power
provided by customers is not stable but the provided -48V DC power is stable
(such as the regions of Africa).
All
power supply cabinets are single-phase input and the power sum of all power
supply cabinets is not more than 15KVA.
Inverters
can only be installed outside cabinets, not inside cabinets and only standalone
inverters can be used.
At
present, the following inverters are available to Huawei: 3KVA, 6KVA and 10KVA.
The power leadin configuration is as follows:
Inverter
|
DC leadin
|
Protection ground cable
|
3KVA
|
1*16mm^2,
blue, one piece
1*16mm^2,
black, one piece
|
1*6mm^2,
yellow and green, one piece
|
6 KVA
10KVA
|
1*35mm^2,
blue, two pieces
1*35mm^2,
black, two pieces
|
1*6mm^2,
yellow and green, one piece
|
The
default configuration terminals for DC leadins and protection ground cables are
OT-xxmm^2-M8 terminals (xx is the cross-sectional
area of cable cores) and they are three times as many as cable cores. For
example, if one 1*16mm^2 blue cable is to be distributed for surveys, the
default configuration is three OT-16mm^2-M8 terminals. Terminals are distributed
to sites without processing.